FL500 UV/IR Hydrogen Flame Detector
The FL500 UV/IR Hydrogen Flame Detector is an Ultraviolet / Infrared flame detector designed specifically to detect hydrogen (H2) fires. The FL500-H2 optical flame detector monitors for radiation emitted by a hydrogen flame in both the ultraviolet (UV) and infrared (IR) spectral ranges. This UV/IR combination provides a fast response time and increased false alarm immunity against sources of radiation for reliable protection.
UV/IR TECHNOLOGY
A UV/IR flame detector combines an ultraviolet (UV) sensor for quick response and an infrared (IR) sensor that monitors radiation emitted by a hydrogen flame. This combination offers increased immunity, operates at faster speeds and is suited for both indoor and outdoor use.
SAFETY INTEGRITY SELF-CHECK
Every two minutes, a built in self-check known as Continuous Optical Path Monitoring (COPM) performs an optical and electrical check to ensure the optical path is clear and the electronic circuitry is operational.
IMPROVED DESIGN
Stainless steel housing, three LED status indicators, reduced footprint, and simplified wiring make the FL500 easy to install and maintain.
RELIABLE TESTING ANYTIME, ANYWHERE
The FL500 can be tested with our exclusive TL105 Test Lamp, which simulates the flickering of a fire. This allows the detector to be tested under simulated fire conditions without the associated risk of an open flame.

FL500 UV/IR H2 Flame Detector Brochure
- Proven Technology. UV/IR flame detection uses an ultraviolet and an infrared detector to monitor for flames increasing false alarm immunity by measuring two different flame spectrums.
- Wide Field of View. 130° cone of vision covers greater distance.
- Safety Integrity Self-Check. Continuous Optical Path Monitoring (COPM) performs self-check every two minutes to ensure the optical path is clear and the electronic circuitry is functional.
- Test Anytime, Anywhere. Easily test with our exclusive TL105 Test Lamp that allows the FL500 UV/IR Flame Detector to be safely tested under real fire conditions with a simulated flicker of a flame.
- Withstands Extremes. Wide operating temperature range (-55°C to +85°C) permits operation in extreme environments.
- Status at a Glance. Three LED status indicators for warning, alarm, and normal operations.
- Rugged Housing. 316 stainless steel housing to withstand the harshest environments
- Multiple Output Options. Industry standard 4-20 mA (source or sink analog), Modbus, HART, relays
Input Power | 20-36 VDC 200 mA max. current (3 W max. power consumption) |
Typical Current | 80 to 150 mA |
Analog Output | Source or Sink |
Analog Signal | 0-20 mA |
Fault Mode | 0-0.2 mA* |
OPM Self-Check Fault | 2 mA, ± 0.2 mA** |
Ready Signal | 4 mA, ± 0.2 mA |
IR Signal | 8 mA, ± 0.2 mA |
UV Signal | 12 mA, ± 0.2 mA |
Alarm Low | 16 mA, ± 0.2 mA |
Alarm High | 20 mA, ± 0.2 mA |
Relay Contact Rating | 5 A 250 VAC 5 A @ 30 VDC resistive (North America), 5 A @ 30 V RMS/42.4 V peak, 5 A @30 VDC resistive (Europe) |
Dip Switch Selectable Options
| Sensitivity Time Delay Alarm Low & Alarm High Relays High, Medium, Low Alarm High 2, 4, 8, or 10 seconds Latching/Non-Latching Energized/De-Energized |
RS-485 Output Modbus RTU | Suitable for linking up to 128 units or up to 247 units with repeaters |
BAUD Rate | 2400, 4800, 9600, or 19200 BPS |
HART | Fully HART 7 Field Comm compliant |
EMC | Complies with EN 50130-4, EN 61000-6-4 |
Cable Requirements | Screened or screened and armoured to BS5308 Part 2, Type 2, or equivalent. |
Status Indicator | 3 LEDs with status, fault, and alarm conditions |
Faults | Monitored Memory checksum, reset line shorted optics blockage, internal voltages, and low supply voltage |
Operating Temperature Range | -55°C to +85°C |
Storage Temperature Range -40°F to +185°F | -40°C to +85°C |
Operating Humidity Range | 0% to 95% RH, non-condensing |
Housing | 316 Stainless Steel, powder coated |
Diameter | 114 mm |
Length | 140 mm |
Weight | 4.0 kg |
Mounting | Stainless steel mounting bracket |
Cable Entry | 2 x 3/4” NPT or 2 x 25 mm |
Standard Configuration | 1.25 mA HART, source current, relays, Modbus, high sensitivity, 4 sec. delay, Hydrogen, 3/4” NPT, mounting bracket |
Wave Lengths | 185 to 260 nm (UV) 2.95 microns (IR) |
Field of View | Up to 130° max. conical |
Fuel | Hydrogen Distance (ft.) Response Time (s) 60 ft (18 m) < 3.0 |
Accessories | Test lamp |
Classification Class | I, Div 1, Groups B, C, D; Class II, Div 1, Groups E, F, G; Class III, Type 6P Ex db IIC T5 Gb; Ex tb IIIC T100°C Db II 2 G D |
Ingress Protection | IP66/IP67 |
Warranty | Three Years |
Approvals | CSA, FM, ATEX, IECEx, INMETRO, CE Marking |
HART | HART 7 registered |
SIL | SIL 3 suitable |