Rebellion Photonics Gas Cloud Imaging Cameras
Rebellion Photonics Gas Cloud Imaging Cameras (GCI) use proprietary hyperspectral imaging technology to capture both visible spectrum and infrared video to monitor, quantify, and display explosive, harmful gas leaks as they occur. Our self-calibrating hardware operates 24/7 in all weather conditions and is typically 100 times more accurate at detecting leaks than traditional hardware, eliminating the need for additional gas detection equipment.
Rebellion Standard Gas Cloud Imaging Camera (GCI)

The Gas Cloud Imaging ( camera, with a range up to 1 700 m, is designed for large sites and extended areas and uses snapshot hyper spectral imaging for real time detection, identification and quantification of gas leaks. Concentration and leak location are provided, and real time alerts create actionable alarms and display live videos of the leak while simultaneously issuing notifications via email or text.
Reliable and robust system designed for large sites and extended areas such as pipelines, ports, refineries, and tank farms. System includes fully automated pan/tilt motors for full coverage of the facility. It is capable to detect gas leaks as far as 1.7 km.
Rebellion Mini Gas Cloud Imaging Camera (GCI)

The smaller version of the Standard GCI camera with wider range of detected gas species. The lightweight mini-GCI is designed for congested areas and smaller sites such as oil rigs & drilling sites, power plants, and LNG facilities.
It can detect gas leaks as far as 100 meters away and is available in explosion-proof certified and non-certified versions.
Concentration and leak location are provided, and real time alerts create actionable alarms and display live videos of the leak while simultaneously issuing notifications via email or text.
Rebellion Mini Gas Cloud Imaging Camera IECEx

The explosion proof version of mini-GCI camera is designed for hazardous locations to operate in all environments.
The mini-GCIx is certified for the most rigorous conditions class I division I. This option is perfect for sites that require certifications such offshore rigs and vessels.
Popular Detectable Gases & Detection Levels
Technical Specifications of Gas Cloud Imaging Camera
Acetic acid | 180 ppm.m |
Ammonia | 13.5 ppm.m |
Benzene | 125 ppm.m |
Butadiene | 125 ppm.m |
Butane | 250 ppm.m |
Carbon Dioxide | 1075 ppm.m |
Ethane | 250 ppm.m |
Ethanol | 15 ppm.m |
Ethylene | 250 ppm.m |
Iso-Butylene | 125 ppm.m |
Iso-Pentane | 40 ppm.m |
Methane | 250 ppm.m |
Methanol | 10 ppm.m |
N-Pentane | 20 ppm.m |
Propane | 500 ppm.m |
Propylene | 125 ppm.m |
Sulfur Dioxide | 20 ppm.m |
Toluene | 150 ppm.m |
Vinyl Chloride | 2.5 ppm.m |
p-or m-Xylene | 20 ppm.m |
Detection Approach | Snapshot Hyperspectral Infrared Imaging |
Detection Time | < 1second |
Field of View | 42.0ox 42.0o |
Position Control | Pan ±180o(360ofull rotation), Tilt ±45o |
Detection Range | Upto 100 m (328 ft) |
Alert/Alarm | Fully automatic alarm with live visual display, audible alert, email, and/or text message |
False Alarm Rate | ≤ 1% |
DCS Integration | Modbus TCP/IP |
Video Output | 160 x 160 pixels (IR) / 640 x 640 pixels (Visible) at 15 Hz |
Weather Conditions | Validatedfor all weather and light conditions |
Temperature Range | -40°C to 55°C (-40°F to 131°F) |
Electrical Requirements | Camera:24 VDC, 17 W Pan/Tilt:24 VDC (Configurationdependent) mini-GCIAnalyzer: 24 VDCor 120/240 VAC, 120 W |
Network Connections | 1 Serial RS-422 + 1 CAT 6 -Pan/Tilt 2 CAT 6 Ethernet Connection -Camera |
Running Time | Continuous (24/7, 365 days) |
Self Calibration | Every 7 & 22 minutes |
Maintenance | No regular maintenance(except exterior cleaning) |
Standard Analyzer | Custom NuvoN5006E |
Analytics | Up to 3 simultaneously;max 7 with enhanced analyzer |
DVR (Video Storage) | Custom Dell PoweredgeR540. Stores up to 5 million detection events with custom auto-erase settings. |