Honeywell FSL100 Flame Detector

The Honeywell FSL100 Flame Detector range of Light Industrial/Commercial Flame Detectors enables simple coverage of fire hazard areas across many fire hazard applications. Installation, set-up and operation are simple. Wide solid area coverage and fast speed of response optimize safety.
With inbuilt automatic test and test lamps available to cover all models, reliability is ensured.
- UV, UV/IR and IR3 Flame Detectors to cover a wide range of applications
- Robust, simple to install & set-up; Wide angle and fast speed of response
- Automatic test and test lamps for simple check and maintenance.
- FSL100 Flame Detectors – UV, UV/IR and IR3 for light industrial applications
- GRP Housing, available in Red or White with optional swivel mount
- 12-14Vdc, 25mA nominal operation
- 4 to 20mA and Relay outputs.
The newest Optoelectronic flame detector for a wide range of Light Industrial fire detection from Honeywell Analytics.
FSL100 range consists of UV, UV/IR and Triple Infra-Red Flame Detectors. All Flame Detectors utilize sophisticated sensing and signal analysis to detect fires quickly while also rejecting false alarms. Due to the FSL100 being small and lightweight, it is very easy to install, but it is designed to work in tough indoor/outdoor environments, as well as potentially explosive atmospheres. With a large field of view it can detect a range of different types of fire including hydrocarbon and non-hydrocarbon sources. Available in UV, UV/IR and 3IR – We have your application covered.
FSL100 Series Flame Detectors - UV, UV/IR, Triple IR
FSL100 UV Flame Detector Features
Suitable for indoor applications; for example fume hoods and hydrogen storage areas
Effective solution for materials burning with low temperatures, e.g.
- Sulphur
- Alarms to fires from heavy hydrocarbons (wood, paper, petroleum, etc.)
- Light hydrocarbons (methanol, methane, etc.), and hydrogen
Good resistance against the influences of:
– Direct and reflected sunlight
– Artificial light, such as fluorescent tubes and glass covered halogen lamps
FSL100 Flame Detector - UV

FSL100 Flame Detector - UV/IR

FSL100 UV/IR Flame Detector Features
Analysis of the flame flicker-frequency for improved false alarm rejection
- Dual sensing methodology enables a wide range of hydrocarbon and non-hydrocarbon fires to be
effectively detected - Good resistance against the influences of:Direct and reflected sunlight
– Artificial light, such as fluorescent tubes and glass covered halogen lamps
– Arcs and electric discharges (static or from e.g. electric motors)
– The radiation from electric welding provided that the electric welding takes place at a distance more than 10 feet from the flame detector (a welding rod contains organic compounds which may produce a small flame)
FSL100 IR3 Flame Detector Features
Analysis of the flame flicker frequency for improved false alarm rejection
- Particularly suited to liquid hydrocarbon and dirty fires
- Affected less by window contamination or smoky fires
- Good resistance against the influences of:
– Direct and reflected sunlight
– Artificial light, such as fluorescent tubes and glass covered halogen lamps
– Arcs and electric discharges (static or from e.g. electric motors)
– The radiation from electric welding provided that the electric welding takes place at a distance more
than 10 feet from the flame detector (a welding rod contains organic compounds which may produce a small flame)
• Especially suitable fires that emit large amounts of smoke
FSL100 Triple IR Flame Detector

FSL100 Flame Detector Test Lamp
FSL100 Flame Detector Specifications
Range: 35 m (IR3), 25 m (UV, UV/IR) alarming within 10 seconds to a 1 ft2(0.1 m2)n-heptane fire
Cone of vision: 90˚minimum horizontal and vertical
Power: 10-28 VDC (12-24 VDC nominal)
Cable entry: M20 clearance. Supplied with gland suitable for cable diameter from 0.2” (5.5mm) to 0.5”(13mm). Terminals suitable for 0.5mm2 (20AWG) to 1.5mm2 (15AWG) wire
Automatic Sensor Test (built in Self-Test) and manual Self-Test
Housing: Glass Reinforced Polyester (GRP), Non-incendive. UV resistant, Self-Extinguishing V–0 (UL-94)
Swivel Mount PA66, UV resistant; Stainless Steel fixings; 280 g

Features of Honeywell FSL100 Flame Detectors
Suitable for Many Applications
- UV, UV/IR and IR3 available
- Hydrocarbon and non-hydrocarbon sources
- Use in potentially explosive atmospheres
- Indoor and outdoor operation
- High visibility red or discrete white models available
Great Performance
- Approved to EN54-10 and FM3260 flame detector standards
- Comprehensive automatic self test
- Remote manual self test option

Fast & Reliable
- High speed sensors and microprocessor
- Sophisticated analysis algorithms
- Continuous health monitoring
- False alarm rejection
Reduced Life Cost - Long life element
- Pressure compensation to avoid contamination
- 2 year warranty
- Buy with confidence
Ease of Installation and Use
- Relay and mA outputs as standard
- Lightweight GRP housing
- Pre-formed knockouts
- Optional swivel mounting bracket
- Long range test lamp available
FSL100 Flame Detector Borchure
Download the FSL100 Flame Detector Brochure direct from Honeywell’s Website – Click Here
- FSL100 Flame Detectors – UV, UV/IR and IR3 for light industrial applications
- GRP Housing, available in Red or White with optional swivel mount
- 12-14Vdc, 25mA nominal operation
- 4 to 20mA and Relay outputs.
Range | 35 m (IR3), 25 m (UV, UV/IR) alarming within 10 seconds to a 0.1 m2 n-heptane fire |
---|---|
Cone of Vision | 90˚minimum horizontal and vertical |
Local LEDs |
|
Current Output | Standard available 4–20 mA (stepped, sinking, non-isolated)
|
Relay Output: Alarm relay & Fault relay | De-energized during normal operation, no alarm, SPDT, 30 VDC – 2 A, 60 W max. Energised during normal operation, no fault, SPDT, 30 VDC – 2 A, 60 W max. |
Cable Gland & Terminals | Cable entry M20 clearance. Supplied with gland suitable for cable diameter from 0.2” (5.5mm) to 0.5”(13mm). Terminals suitable for 0.5mm2 (20AWG) to 1.5mm2 (15AWG) wire |
Start Up Times | <10 sec |
Alarm Response Time | 8 to 30 sec |
Alarm Output Settings | Selectable LEDs and relays latching/non-latching; factory setting: latching |
Automatic & Manual Self-Test | Automatic Sensor Test (built-in Self-Test) and manual Self-Test |
Operating Current Normal | 25 mA at 24 VDC |
Current in Alarm, at 24 VDC | ±75 mA at 24 VDC |
Connections to: |
|
End of Line and Alarm Resistor | To be adjusted to the fire control panel; free terminals are dedicated to the resistors. Note: the alarm and EOL resistor must be rated 2 W min. each and the total power dissipation of both alarm and EOL resistor should not exceed 2 W |
Housing | Glass Reinforced Polyester (GRP), Non-incendive. UV resistant, Self-Extinguishing V–0 (UL-94) |
Swivel Mount | PA66, UV resistant; Stainless Steel fixings; 280 g (0.62 lb) |
Pressure Compensating Element | PCE (Pressure Compensating Element) avoids moisture build-up in the detector housing due to changes in ambient air pressure |
Dimensions | 125 x 80 x 57 mm |
Weight | 465 g |
Ingress Protection | IP65 |
Temperature, Operating | –40 ˚C to +70 ˚C |
Temperature, Ambient ATEX and FM Class 3611 | –25 ˚C to +70 ˚C |