Honeywell Touchpoint Plus Controller

PSS is a supplier the Honeywell Touchpoint Plus Controller for gas detection applications. The Honeywell Touchpoint Plus Controller takes the user experience to the next level. With its unique user interface, operators are able to take control of their gas detection system, safe in the knowledge that their site and staff are protected and productivity is maintained.
Designed to work across multiple industries, Touchpoint Plus’Controller’s modular architecture enables you to customize your system to meet your specific application requirements.
Large touchscreen LCD
Built around its intuitive, ergonomic touchscreen, Touchpoint Plus is designed for ease. From here operators can configure, operate and maintain their gas detection system simply and efficiently by simply touching the screen. The multilingual interface simplifies operation, reducing training requirements and costs. Real-time data is presented in an easy to navigate menu system, whilst historical data can be downloaded to monitor developing threats.
Small Stand Alone or Integrated Systems
At a glance system visibility
When fast and informed decisions need to be made, Touchpoint™ Plus’ full color traffic light style status indicators provide clarity from a distance allowing operators to see system status at-a-glance and make time critical decisions easily.
If you need to integrate your gas detection with a higher level management system, the Modbus output option makes this straightforward.
Unique industrial design
Made of high-impact polymer plastic, Touchpoint™ Plus is versatile and durable. It is dust-proof, water-proof and has been tested to withstand the toughest environments in which our customers operate – indoors and out. Touchpoint™ Plus can be directly wall mounted, or for an easier 1-man installation there is an optional mounting plate. Behind the hinged front cover there is plenty of space for wiring and a unique tiered terminal arrangement for easy access. Cable entries are pre-drilled and sealed ready to use, further reducing installation time and cost.
Full system solution
Touchpoint™ Plus provides a reliable safety solution for small scale gas detection systems across a wide range of applications and industries. As the heart of your gas detection system, Touchpoint™ Plus is designed to work with Honeywell’s industry leading gas detectors and drive actuators, audible and visual alarms to provide a complete end-to-end, highly configurable safety solution.
Download the Brochure Direct from Honeywell’s Website by Clicking the Link

- Colour LCD Touch Screen
- AC or DC power options
- Battery back up option
- Password protection
- Up to 16 Analog Input channels*
- mA or mV inputs
- 2 or 3-wire signal inputs
- Relay outputs
- Analog outputs
- Alarm update on Acknowledge via local or remote inputs
- Automatic Self-Diagnostic with error codes
- SD Card for event recording, data transfer and printing
| Number of Detectors | Up to 8 channels with base unit, up to 16 channels with expansion unit* |
|---|---|
| Type of Inputs | 2 or 3 wires, mA, mV, max. 15W per channel, max 40W total (with dedicated A/V drive) / 68W total (without dedicated A/V drive) |
| Size (wall-mounted version) | 426 mm × 300 mm × 156 mm |
| Housing Material | Polycarbonate ABS |
| Weight | Max 8.5 kg |
| Display | 7’’ color LCD touchscreen. Graphic User Interface |
| Visual Indicators | 3 LEDs for master indicators. LED for each channel. Green: Normal; Yellow: Fault: Inhibit; Red: Alarm |
| Audible Alarm | ≥ 70dB @ 1m |
| Button | Common for reset/mute operation |
| Language | English, French, German, Italian, Dutch, Spanish, Portuguese, Russian, Chinese |
| Power AC | 110/220VAC, 50-60Hz Manual switching |
| Power DC | 18 to 32 VDC (+/-10%) Typical 24VDC |
| Power Consumption | Max 105W (including detector and external devices) |
| Operating | -10°C to +55°C (14°F to +131°F) continuous, up to 95% RH (non-condensing), IP65 and NEMA 4X |
| Storage | Instrument -25°C to +60°C. (-13°F to +140°F), up to 95% RH (non-condensing) |
| 4-20mA Input | 2 or 3 wire, 2/4/8 channel modules |
| mV Input | Catalytic type flammable gas detectors (Honeywell models). 2/4/8 channel modules |
| Dual Input | 2 channel mA + 2 channel mV module or 4 channel mA + 4 channel mV module |
| Relay Output | 12 or 24 relay outputs, NO/C/NC changeover, 5A@30VDC/250VAC, user-configurable – energized/de-energized, latching/non-latching, time delay |
| 4-20mA Output | 4 or 8 isolated repeated mA outputs, 0-22mA, 0-100%FSD = 4-20mA |
| Common Inputs | Remote reset, remote inhibit |
| Common Outputs | Four powered A/V outputs for alarms and fault, three common alarm outputs |
| Backup Battery | 22.2V Lithium-Ion Battery, 2600mAh capacity (>30 minutes for a typical system) |
| Data logging | Configuration logged events and data |