TouchpointPlus-Wireless-Controller

Touchpoint Plus Wireless Controller

The Touchpoint Plus Wireless Controller is the command-and-control element of the Mesh system that gathers data and monitors alarms from Mesh-enabled toxic and flammable gas monitors. The built-in wireless modem automatically links with Mesh-enabled monitors, and the controller has built-in security safeguards to resist tampering.

The Honeywell Touchpoint Plus Wireless Controller does have additional 8 analogue 4-20 mA inputs for combination of traditional wired products and wireless products.

Features of the Honeywell Touchpont Plus Wireless Controller

Touchpont Plus Wireless Controller Easy to Use Touch Display

Versatile

  • Built-in wireless modem for use in Mesh networks
  • Manages up to 64 channels
  • Up to 15 programmable SPDT relay outputs
  • RS-485 and Ethernet interface
  • 8 analogue 4-20 mA inputs
  • Meteorological data sensors
  • IP 65 rated

Easy to Use

  • Backup battery for up to 12 hours of operation depending on configuration
  • Built-in data logging
  • C1D2 certified
honeywell touchpointplus controller

Touchpoint Plus Wireless Controller Brochure

Download the Product Brochure direct from Honeywell’s Website by Clicking Here

Touchpoint Plus Wireless Controller Technical Specifications

Capacity

Up to 8 channels with the base unit

Size (Wall-Mounted Version)

426 mm x 300 mm x 156 mm

Housing Material

Polycarbonate ABS

Weight

Max. 8.5 kg

Display

7″ color LCD touchscreen. Graphic User Interface

Visual Indicators

3 LEDs for master indicators. LED for each channel. Green: Normal; Yellow: Fault: Inhibit; Red: Alarm

Audible Alarm

≥ 70dB @ 1 m (3.28 ft)

Button

Common for reset/mute operation

AC Power

110/220 VAC, 50-60 Hz Manual switching

DC Power

18 to 32 VDC (+/-10%) Typical 24 VDC

Power Consumption

Max. 105 W (including detector and external devices)

Operating

-10 °C to +55 °C (14 °F to +131 °F) continuous, up to 95% RH (noncondensing), IP65 certified

Storage

Instrument -25 °C to +60 °C (-13 °F to +140 °F), up to 95% RH (non-condensing)

4-20mA Input

2- or 3-wire, 8 channel modules

Relay Output

NO/C/NC changeover, 1.7 A @ 30 VDC/250 VAC, user-configurable – energized/deenergized, latching/non-latching, time delay

Common Inputs

Remote reset, remote inhibit

Common Outputs

4 powered A/V outputs for alarms and fault, 3 common alarm outputs

Electromagnetic Compatibility and Electrical Safety Approvals

EMC/RFI (EN 50270:2015)

LVD (EN 61010-1:2010)

CSA-C22.2 No. 61010-1-04

UL 61010-1 (3rd Edition) and 508

Hazardous Location Approvals

Class I, Division 2, Group A, B, C, and D, or non-hazardous only

Backup Battery

22.2 V Lithium-Ion Battery, 2600 mAh capacity (12 hours for the wireless system)

Datalogging

Configuration, logged events, and data

Communication

MODBUS TCP, WEB monitoring, and MODBUS RTU

Radio model

RM2400 / RM2400A

Radio Frequency

2.4 GHz IEEE 802.15.4

Frequency Range

2.400-2.4835 GHz

Frequency Channels

Frequency band has 16 available channels

Transmission Range

Up to 300 meters line of sight

Receiver Sensitivity

Minimum of -95 dBm at 2.4 GHz

Modulation

802.15.4 DSSS BPSK

Transmit Power

802.15.4 DSSS BPSK

Transmit Power

20 dBm

Data Rate

250 kbps